GENERAL
The AFP-200 is a compact, cost-effective, intelligent fire alarm control with a capacity of 198 individually identified and controlled points and an extensive list of powerful features. The AFP-200 provides capabilities that exceed most large intelligent systems, at a cost comparable to conventional control panels.
FEATURES
198 intelligent device capacity (99 analog detectors and 99 monitor/control modules). Style 4, 6, or 7.
Overall 301 point capability (198 intelligent points, 4 programmableNAC circuits, 99 programmable relays).
Network ready (reference NOTIFIRENET and NAM-232 data sheets for more information).
Intelligent features: Manual sensitivity adjustment.
- Day/Night automatic sensitivity adjustment.
- Drift compensation (U.S. Patent Pending) meets UL requirements as a calibrated test instrument.
- Auto detector test (meets NFPA 72).
- Maintenance alert (two separate algorithms).
- Pre-alarm (AWACS U.S. Patent Pending).
- Activate local sounder base on pre-alarm.
- LED blink control for sleeping areas.
- Automatic device type check.
Releasing features:
- Four independent hazards.
- Sophisticated cross-zone (three options)
- Delay timer and Discharge timers (adjustable).
- Abort (four options).
Optional DACT, with AC fail delay.
LCD-80 remote display/control.
ACS annunciators (EIA-485), including LDM custom.
Printer interface (80-column and 40-column printers).
5.0 A usable regulated output power, plus 6.0 A expander(maximum 8.0 A to panel circuits).
80-character LCD display, backlit.
Real-time clock, with European format option.
History file with 650-event capacity in nonvolatile memory. Includes non-erasable shadow history.
Waterflow or supervisory selection per point.
Alarm Verification selection per point, with tally.
Walk Test reports two devices set to same address.
Positive Alarm Sequence (PAS) Presignal per NFPA 72.
Silence inhibit and Auto Silence timer options.
March time/temporal/California code for bell circuits.
Field-programmable on panel or on PC, with user-defined passwords, plus Autoprogram feature.
UL-Listed modem interface allows remote/off-site system integration.
FZM-1 two-wire detector interface provides compatibility with many non-NOTIFIER detectors for retrofit applications (consult factory for latest compatibility listings).
Dual-rate charger for up to 90 hours of standby power.
Two-Stage option for notification circuits (Canada).
Tornado Warning activates different notification circuit code.
Non-alarm points for lower priority functions.
Remote Silence/Reset/Evacuate via monitor modules.
Automatic time control functions, with holiday exceptions.
Rapid poll algorithm for manual stations. Responds in < 2 seconds.
Operates with untwisted, unshielded wire (up to 1,000 ft./304.8 m) for retrofit applications (U.S. Patent 5, 210, 523).
UL Listed for Fire Signaling per Standard 864 & NFPA 72.
UL Listed for Burglary applications per Standard 1076.
UL Listed for Releasing Service. Complies with NFPA 12, 12A, 12B, 13, 15, 16, 17, 17A, 2001 Standards when installed in accordance with appropriate NFPA standard.
Approved for Agent Release and Preaction/Deluge by CSFM, City and County of Denver, FM, MEA, and ULC.
Approved for marine applications by U.S. Coast Guard andLloyds Register of shipping.
SPECIFICATIONS
Primary input power, 120 VAC, 50/60 Hz, 3.0 A; for AFP-200E: 230 VAC, 50/60 Hz, 1.5 A.
Total Internal 24 VDC Power: 5.0 A (total shared power). High-ripple regulated power: 1.5 A (suitable for EIA-485 devices, except ACM-8R); 1.0 A maximum standby.
Non-resettable power: 500 mA.
Four-wire smoke detector power: 500 mA.
Four built-in notification circuits:
NAC Circuit 1: 2.25 A.
NAC Circuits 2-4: 2.25 A (shared total).
NOTE: with optional APS-6R Power Supply NAC circuits 3 & 4 are expanded to 3.0 A (8.0 A total power).
Battery charger range: 7 AH - 18 AH.
Charge high rate: 29.1 V. Float rate: 27.0 V.
Relay contact rating: 2.0 A @ 30 VDC.
Cabinet dimensions: 16.125" (40.958 cm) high x 14.5" (36.83 cm) wide x 5.5" (13.97 cm) deep.
SYSTEM CAPACITY
Total programmable input/output points: 301
Intelligent detectors: 99
Addressable monitor/control modules: 99
Programmable NAC circuits in panel: 4
Programmable software zones: 99
Programmable remote relay/annunciator points: 99
LCD-80 annunciators per system: 4
ACS annunciators per system: 10
CONTROLS AND INDICATORS
6 LED indicators: AC Power; Fire Alarm; Pre-Alarm; Supervisory/Security; Alarm Silenced; System Trouble.
21 Membrane Switch Controls: Acknowledge/Step; Silence; Evacuate; System Reset; 12-key Alpha pad; 4 cursor keys;Enter.
LCD Display: 80 characters (4 x 20) with long-life LED backlight.